J030--Generator-ATS Maintenance (VA-27-00002745)
Key Dates
Due Date
-
Posted Date
-
Agency & Value
Agency
NAC FACILITY PURCHASING SUPPORT (36S797)
Contract Value
Not provided
Codes & Classification
Solicitation Number
36S79726Q0006
NAICS
561210 - Facilities Support Services
Classification Code
J030
Additional Details
The Department of Veterans Affairs (VA), through its NAC Facility Purchasing Support office, has issued a combined synopsis/solicitation for comprehensive Generator and Automatic Transfer Switch (ATS) Maintenance services at the Edward Hines VA facility in Hines, Illinois. This procurement, identified under solicitation number 36S79726Q0006, is classified under NAICS code 561210 (Facilities Support Services) and Product Service Code J030, and is set aside exclusively for Service-Disabled Veteran-Owned Small Business Concerns (SDVOSBC).
The primary objective of this contract is to ensure the reliable operation and regulatory compliance of all backup generators and associated ATS equipment supporting critical VA operations, including the Consolidated Mail Order Pharmacy (CMOP). The scope of work encompasses scheduled preventive maintenance, unscheduled repairs, annual load-bank testing, transformer inspections (including infrared scanning), and the provision and replacement of consumables necessary for generator and ATS upkeep.
Key requirements and deliverables include:
- **Preventive Maintenance (PM):** Monthly PM is required for two 600 kW generators and one 500 kW generator, specifically scheduled on the second Tuesday of each month from 4:00 AM to 7:00 AM to accommodate the operational needs of the CMOP. The 1250 kW and 750 kW generators may be serviced during normal business hours. All maintenance for the CMOP generators must be prioritized and completed before the start of the production line to avoid operational delays.
- **Annual Load-Bank Testing and ATS Maintenance:** These activities, along with sampling and other annual maintenance tasks, may be performed during normal business hours unless otherwise coordinated with the Contracting Officer’s Representative (COR).
- **Transformer Inspections:** The contract includes quarterly energized transformer inspections, with one of the quarterly services incorporating an annual inspection and infrared (IR) scan. The annual IR scan of transformer lugs and ATSs must be performed while the equipment is energized, prior to de-energizing for maintenance, to identify potential faults under load. Any issues detected are to be addressed during the scheduled de-energized maintenance period.
- **Consumables:** The contractor is responsible for furnishing and replacing all consumables identified in Attachment B during preventive maintenance, with these costs to be included in the applicable PM Contract Line Item Number (CLIN) pricing. Consumables include items such as filters and oil, with repairs and replacement of certain parts (e.g., hoses and belts) to be quoted and approved separately as needed.
- **Unscheduled Repairs:** A dedicated CLIN for unscheduled maintenance is included, with a funding item of $50,000 to address unforeseen repairs throughout the contract period.
- **Emergency Response:** Contractors are expected to include local labor and emergency travel costs in their quotes, as the VA has historically relied on local labor for such needs.
- **Fuel Provision:** The VA will furnish all diesel fuel required for generator operation during inspections and maintenance activities.
All generators at the facility are diesel-powered, with voltages of 480V and 240V. There are no access difficulties for any units, as all are within 50 feet of an entry door suitable for truck parking. The facility will provide detailed information on generator models, serial numbers, and equipment age in Attachment A of the solicitation package. Previous maintenance reports and records of emergency calls or major repairs will be made available to the awarded contractor.
The contract is managed by the NAC Facility Purchasing Support office, with Michelle Williams serving as the primary point of contact ([email protected], 708.786.7565). The solicitation is currently active, with a response deadline of October 19, 2026.
This opportunity is well-suited for SDVOSBs with demonstrated expertise in generator and ATS maintenance, particularly those experienced in supporting mission-critical healthcare or government facilities. Contractors should be prepared to deliver comprehensive preventive and corrective maintenance, coordinate closely with facility operations to minimize downtime, and manage all aspects of compliance, safety, and documentation as outlined in the solicitation and its attachments.
For further details, including access to all solicitation attachments, interested parties should refer to the official notice on SAM.gov at https://sam.gov/opp/35c6be52408641d5bcbc093d514058e4/view.
Documents9