Modular Three-Phase Uninterruptible Power Supply (UPS) System
Key Dates
Due Date
-
Posted Date
-
Agency & Value
Agency
FA8307 AFLCMC HNCK C3IN
Contract Value
Not provided
Codes & Classification
Solicitation Number
FA830726QB087
NAICS
335311 - Power, Distribution, and Specialty Transformer Manufacturing
Classification Code
6130
Additional Details
Documents2
The Department of the Air Force, through the Air Force Life Cycle Management Center (AFLCMC), Cryptologic and Cyber Systems Division Contracting Office (AFLCMC/HNCK), has issued a combined synopsis/solicitation (FA8307-26-Q-B087) for the procurement and installation of a Modular Three-Phase Uninterruptible Power Supply (UPS) System. This requirement is being solicited as a Request for Quotation (RFQ) under full and open competition, with no set-aside restrictions, and will result in a single firm-fixed-price purchase order. The procurement is governed by the Revolutionary Federal Acquisition Regulations Overhaul (RFO) and the Revolutionary Defense Federal Acquisition Regulation Supplement (R-DFARS), with all applicable clauses and provisions incorporated by reference.
**Purpose and Scope**
The primary objective of this procurement is to enhance the reliability and resilience of critical power infrastructure at the ITAC INE test center, located at Joint Base San Antonio-Lackland, Texas. The selected contractor will provide a modular, high-efficiency three-phase UPS system with a capacity of 40 kVA to 60 kW, including all necessary components and installation services. The system is intended to ensure uninterrupted power for mission-essential operations, supporting the Air Force’s ongoing commitment to operational continuity and cyber resilience.
**Key Requirements and Deliverables**
The scope of work encompasses the supply, delivery, and installation of a modular three-phase UPS system with the following essential features:
- **Capacity and Configuration:** The UPS must provide a minimum of 40 kVA/kW, supporting a 208V-208V 4-wire plus ground input/output configuration.
- **Battery Solution:** The system must include either an integrated or external battery solution, utilizing VRLA or Lithium-Ion technology.
- **Maintenance Bypass Cabinet (MBC):** A right-attached MBC with an integrated 250A panelboard is required, facilitating maintenance without service interruption.
- **Efficiency:** The UPS must achieve at least 97.5% efficiency in double-conversion mode, with an energy optimization (Eco-Mode) capability up to 99%.
- **Safety and Controls:** The system must be UL 1778 listed, provide a minimum 65kAIC interruption rating, and feature a local touchscreen HMI. Network connectivity must support SNMP, Modbus, and BACnet protocols.
- **Seismic Compliance:** Optional bracket kits must be included to meet local seismic certification standards at Lackland AFB.
- **Airflow and Cable Management:** The design must utilize front-to-top airflow and ensure that no cords or cabling are routed along the ground, maintaining clear pedestrian walkways.
- **Site Considerations:** Installation must avoid disturbing any Class II Asbestos Containing Material (ACM).
**Performance and Delivery**
- **Period of Performance:** Delivery and installation are expected within 30 to 60 days after receipt of order (ARO).
- **Inspection and Acceptance:** All work will be inspected and accepted at the destination.
- **FOB Terms:** Destination.
- **Packing/Packaging:** Must comply with ASTM D3951 commercial standards.
- **Marking and Consignment:** Shipments must be properly marked and consigned as instructed.
- **Long-Lead Items:** Offerors are required to identify any potential long-lead items, such as large-frame battery cabinets, that could impact the deployment schedule.
- **Payment:** All payments will be processed electronically via Wide Area WorkFlow (WAWF).
- **Price Validity:** Quoted prices must remain valid for 30 days.
**Contracting Entity and Location**
- **Contracting Office:** AFLCMC/HNCK C3IN, Department of the Air Force, Department of Defense
- **Place of Performance:** ITAC INE test center, 230 Hall Blvd, Bldg 2028, Ste. 128, San Antonio, TX 78243-7052
- **PSC/FSC:** 6130 (Converters, Electrical, Nonrotating)
- **NAICS:** 335311 (Power, Distribution, and Specialty Transformer Manufacturing)
**Contact Information**
- **Primary Contact:** Ms. Rachel J. Sexton, [email protected], 210-925-0743
- **Secondary Contact:** Victor Quiroz, [email protected], 210-925-0723
**Procurement Process and Considerations**
This solicitation is issued as a combined synopsis/solicitation under commercial acquisition procedures. All interested and capable firms, regardless of size or socioeconomic status, are encouraged to respond. Offerors must indicate their business size and ownership status (large, small, small-disadvantaged, 8(a), woman-owned, U.S. or foreign owned). Registration in the System for Award Management (SAM) is mandatory prior to award.
The Government will evaluate quotes based on best value, considering both technical capability/acceptability and price. The anticipated award will be a single firm-fixed-price purchase order. All applicable federal, defense, and agency-specific clauses and provisions apply, including those related to equal opportunity, sustainable products, Buy American/Trade Agreements, and electronic payment.
**Submission Instructions**
Quotes must be submitted electronically to the designated contacts by 27 July 2026, 16:00 CST. Required forms (DD Form 1653 and AFMC Form 158) are attached to the solicitation. The opportunity remains active and is posted on SAM.gov under Opportunity ID a02bec9931ed47cd8e635fcb71af3f24.
**Ombudsman**
An AFLCMC Ombudsman is available to address concerns regarding this acquisition. Before contacting the Ombudsman, parties should first seek resolution with the Contracting Officer. The Ombudsman can be reached at AFLCMC/AQ-AZ Workflow ([email protected]) or 937-255-5512/DSN 785-5512.
**Summary**
This procurement represents a critical infrastructure investment for the Air Force, seeking a qualified contractor to deliver and install a state-of-the-art modular UPS system at Lackland AFB. The requirement is technically rigorous, emphasizing high efficiency, safety, maintainability, and compliance with all applicable standards. Contractors with demonstrated experience in power systems integration, commercial UPS solutions, and secure, compliant installation practices are encouraged to review the solicitation in detail and consider submitting a proposal.