J045--Newington Boiler Plant Steam Header Valves Extension
Key Dates
Due Date
-
Posted Date
-
Agency & Value
Agency
241-NETWORK CONTRACT OFFICE 01 (36C241)
Contract Value
Not provided
Codes & Classification
Solicitation Number
36C24126Q0475
NAICS
238220 - Plumbing, Heating, and Air-Conditioning Contractors
Classification Code
J045
Additional Details
Documents2
The Department of Veterans Affairs (VA), through its Network Contract Office 01, is soliciting proposals for the correction of header deficiencies at the Boiler Plant Steam Header Valves at the VA Connecticut Healthcare System’s Newington Campus, located at 555 Willard Avenue, Newington, CT 06111. This procurement is issued as a combined synopsis/solicitation under solicitation number 36C24126Q0475, and is designated as a Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside, in accordance with NAICS code 238220 (Plumbing, Heating, and Air-Conditioning Contractors), with a small business size standard of $19 million.
**Purpose and Scope**
The primary objective of this contract is to ensure the continued safe, efficient, and compliant operation of the facility’s high-pressure steam boiler plant system. The project addresses deficiencies in the steam header and associated valves, requiring assessment, removal, and replacement to meet VA Directive 1810 and all applicable codes and regulations. The scope encompasses the provision of all labor, materials, equipment, tools, supervision, and incidentals necessary to complete the work, including safety procedures, daily clean-up, and proper disposal of waste.
**Key Requirements and Deliverables**
Contractors must remove and replace a total of eleven (11) valves as identified during a field review with the Plant Supervisor and Contracting Officer’s Representative (COR). Of these, nine valves will be supplied by the facility, while the contractor is responsible for procuring two 4-inch valves and all required hardware (nuts, bolts, gaskets, etc.). All elevated valves must be installed with chain wheels and pull chains for safe access, and hammer blow chain wheels are required to facilitate operation of stuck valves. Double inline valve installation is mandated for isolation of high-pressure steam lines, and all work must be coordinated with the Plant Supervisor and COR.
Additional requirements include:
- Installation of serviceable insulation with Velcro straps, flow indicators, labeling, color coding, and brass tags.
- Compliance with VHA Directive 1810(1), prohibiting the use of cast iron fittings and pipe components except in specific, approved repair instances.
- Use of ASTM A193 bolts for steam piping hardware, replacing any ASTM A307 bolts.
- All new steam and condensate lines must be Schedule 80, with welded connections preferred.
- All repairs and modifications must adhere to ASME and NBIC standards.
- Certified welders with R-stamp certification are required, and all welds must meet ASME Section V and VIII standards.
- Submission of a comprehensive final report detailing repairs, testing, and photographic documentation within fourteen (14) business days of completion.
- Material certifications for replacement parts and waste manifests must be provided.
**Contractor Qualifications**
Eligible bidders must have a field service representative located within 100 miles of the Newington Campus. Contractors must demonstrate at least three years of relevant experience with commercial and industrial steam boiler systems, including installation, repairs, inspections, cleaning, calibration, and testing. Industry-standard certifications, including OSHA (minimum 10 hours, 30 hours preferred) and R-stamp for welders, are required. Documentation of technical training and certifications must be submitted for review and acceptance prior to commencement of work.
A mandatory pre-bid site visit is scheduled for May 13, 2026, at 8:30 a.m. at the Newington Campus, E Building 3, 3rd Floor, to ensure bidders are familiar with site conditions and requirements.
**Contract Administration and Compliance**
The contract will be awarded as a firm-fixed price agreement, with a period of performance of 45 days from contract award and Notice to Proceed. All work must be scheduled between 7:00 a.m. and 5:00 p.m., Monday through Friday, and coordinated with the COR. Off-normal hours and work on federal holidays require prior approval.
Contractors must comply with VA policies for confined space entry, Lock Out Tag Out (LOTO), and hot work permits, as well as all applicable safety codes, environmental abatement requirements, and VA security protocols. All personnel must check in daily, obtain temporary identification badges, and adhere to site-specific rules, including restrictions on smoking, photography, and parking.
**Evaluation Criteria**
Proposals will be evaluated based on price, past performance, and technical capability. Offerors must submit a completed price schedule, past performance worksheet (with up to three references for similar work), and demonstrate their experience and qualifications in accordance with the Performance Work Statement. Subcontracting plans, if applicable, must be disclosed.
**Contracting Entity and Contact Information**
The contracting entity is the VA Network Contract Office 01 (36C241), a federal office under the Department of Veterans Affairs. The primary point of contact for this solicitation is Nathan Langone, reachable at [email protected] or 603-624-4366.
**Submission Instructions and Deadlines**
Quotes must be submitted electronically via email to [email protected] by May 27, 2026, at 10:00 AM EST. Late submissions will not be considered. All offerors must be registered in the System for Award Management (SAM) and comply with VA’s VISTA system for purchase orders and invoice processing.
**Constant Elements Throughout Contract Lifecycle**
Throughout the contract, adherence to VA standards, federal regulations, and site-specific safety and security protocols will remain paramount. The contractor is expected to maintain compliance with all codes, provide required documentation, and coordinate closely with VA personnel to minimize operational disruptions. All deliverables, records, and data generated under the contract are the property of the U.S. Government, and contractors must comply with federal records management and privacy requirements.
**Summary**
This opportunity is well-suited for experienced, certified contractors specializing in steam boiler plant systems, particularly those with prior VA project experience and a local presence. The project demands technical expertise, rigorous safety compliance, and thorough documentation, with a clear focus on maintaining operational integrity and regulatory compliance at the VA Connecticut Healthcare System’s Newington Campus.
For full details and attachments, interested parties should refer to the official notice at https://sam.gov/opp/5bb7a500a4a347938167a6b79040e307/view.