The U.S. Army Corps of Engineers (USACE), Portland District, has announced its intent to solicit proposals for the repair and refurbishment of Generator Step-Up (GSU) power transformers at The Dalles Dam, located in The Dalles, Oregon. This presolicitation notice outlines a forthcoming opportunity for qualified contractors to undertake critical maintenance and restoration work on two primary GSU transformers (T9 and T10), with an option to include a third unit (T11), all of which are essential components of the dam’s hydroelectric power generation infrastructure.
The primary objective of this procurement is to restore the reliability and extend the operational life of these large, Class II oil-filled power transformers, each rated at 230 kV and 208 MVA, originally manufactured by General Electric in 1973. The need for this project arises from previous transformer failures and subsequent forensic investigations that identified significant deterioration, particularly in high-voltage neutral conductor components. The intended outcome is to return these transformers to dependable service, ensuring continued safe and efficient power generation at the facility.
The scope of work is comprehensive and includes all labor, supervision, equipment, materials, transportation, testing, engineering support, and incidental services necessary for the inspection, repair, refurbishment, and testing of the transformers. Key requirements and deliverables include:
- Detailed internal inspection of the transformers and preparation of thorough inspection and repair reports.
- Engineering evaluation of transformer condition and recommendations for repair actions.
- Repair and refurbishment of the transformers, including removal, inspection, repair, replacement, and reinstallation of high-voltage and low-voltage bushings.
- Removal and reinstallation of transformer-mounted devices and accessories.
- Replacement of gaskets and repair or replacement of internal transformer conductors as needed.
- Evaluation of windings, connections, terminals, and insulation systems for signs of overheating, deterioration, or other damage.
- Management of transformer oil, including draining, temporary storage, containment, disposal, vacuum processing, hot-oil filling, and installation of new insulating oil.
- Comprehensive electrical and oil testing before and after repairs, such as insulation resistance, power factor, winding resistance, turns ratio, bushing power factor, leakage reactance, and Sweep Frequency Response Analysis (SFRA).
- Preparation and submission of test reports and documentation to demonstrate successful completion of all repair activities.
- Optional tasks, including replacement of oil cooling pump isolation valves and repair/refurbishment of the third transformer (T11).
Contractors may choose to perform the refurbishment on-site or transport the transformers to an off-site repair facility. Should off-site work be selected, the contractor will be responsible for all aspects of transportation, rigging, logistics, environmental compliance, security, and restoration associated with moving the equipment.
This procurement will be conducted as a competitive negotiated acquisition, utilizing a Best Value Tradeoff source selection process. The contract will be awarded as a Firm-Fixed-Price construction contract. The applicable North American Industry Classification System (NAICS) code is 238210 (Electrical Contractors and Other Wiring Installation Contractors), with a Small Business Administration (SBA) size standard of $19.0 million. The Product Service Code (PSC) is Z2MD, denoting repair or alteration of electric power generation facilities—hydroelectric. There is no set-aside for this procurement; all qualified firms are encouraged to participate. The estimated magnitude of construction is between $5,000,000 and $10,000,000.
The work will be performed within an active federal hydroelectric facility, requiring strict adherence to all safety, security, environmental, and operational protocols as specified in the solicitation documents. Performance and payment bonds will be required, and applicable wage determinations and labor requirements will be incorporated into the solicitation. A site visit is anticipated post-solicitation, with details to be provided in the official solicitation package.
Interested contractors should note that all solicitation materials, including specifications, drawings, and amendments, will be made available electronically via SAM.gov. It is the responsibility of interested parties to monitor SAM.gov for updates.
The contracting entity for this opportunity is the U.S. Army Corps of Engineers, Portland District (W071 ENDIST PORTLAND), under the Department of the Army, Department of Defense. The primary point of contact is Joseph B. Jarvis ([email protected]), with secondary contact Cory Pfenning ([email protected]).
This notice is issued solely for informational and planning purposes and does not constitute a solicitation. The government reserves the right to cancel this requirement at any time, and no reimbursement will be made for any costs incurred in response to this notice or in preparation for any future solicitation.
Contractors with demonstrated experience in the inspection, repair, and refurbishment of large, high-voltage, oil-filled power transformers—particularly within hydroelectric or similar high-voltage industrial environments—are encouraged to review this opportunity and monitor SAM.gov for the forthcoming solicitation.