K063--Crescent House EST4 Fire Alarm Upgrade
Key Dates
Due Date
-
Posted Date
-
Agency & Value
Agency
241-NETWORK CONTRACT OFFICE 01 (36C241)
Contract Value
Not provided
Codes & Classification
Solicitation Number
36C24126Q0434
NAICS
561621 - Security Systems Services (except Locksmiths)
Classification Code
K063
Additional Details
Documents2
The Department of Veterans Affairs, through its 241-Network Contract Office 01, has issued a combined synopsis/solicitation for the Crescent House EST4 Fire Alarm Upgrade, procurement identifier 36C24126Q0434. This opportunity is specifically set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBC), aligning with NAICS code 561621 (Security Systems Services, except Locksmiths), and classified under Product Service Code K063.
The primary objective of this procurement is to upgrade the fire alarm system at Crescent House, ensuring compliance, uniformity, and enhanced safety for residents. The scope of work centers on replacing the existing fire alarm control panel with an Edwards EST4 model, as explicitly required by the solicitation. No alternative panels, even if manufacturer-supported and UL-listed, will be accepted; this stipulation is intended to maintain system uniformity across multiple VA facilities and sites, which is a strategic priority for the agency.
The upgrade encompasses a single-floor unit of approximately 1,100–1,200 square feet, containing five rooms (including two bedrooms) and drop ceilings. Apartment 110, which is one unit away from the main panel, is a focal point due to a known MAP fault and other troubleshooting needs. The unit contains five peripheral devices: one addressable and two non-addressable smoke detectors, one horn/strobe, and one pull station. Replacement of all peripherals is already included elsewhere in the contract, and the solicitation allocates 10 man-hours for any remaining troubleshooting or repairs related to wiring or programming. Should unforeseen issues exceed this allocation, the government will not require the contractor to absorb indefinite repair costs; instead, additional work may be handled through contract modification or separate solicitation.
The solicitation clarifies several technical requirements and expectations:
- The non-addressable smoke detectors are independent, not tied into the fire alarm panel, and serve to alert residents of cooking-related incidents before triggering the addressable detectors.
- Existing field wiring issues, such as ground faults, will not be covered beyond the allotted troubleshooting hours; significant wiring replacement would be handled separately.
- The primary style sprinkler heads currently installed are Viking VK302, Model M, 5.6K, Standard Pendent, QR, ½ NPT, Chrome, 155°F, or equivalent.
- Horn/strobe units in Apartment 110 must be replaced with identical or superior units to meet NFPA 72 requirements for multi-bedroom notification.
- Shop drawings must be approved by the VA, which serves as the Authority Having Jurisdiction (AHJ) for this project.
- A minimum one-year warranty is required for all equipment and installation labor, including any reused or reinstalled components. The warranty does not extend to untouched existing devices.
- Post-installation technical support is limited to a one-hour exit briefing for staff, during which documentation, manuals, and certificates will be handed over. Any additional support beyond this is subject to contract modification or a fixed-price line item.
- The system is confirmed to be a horn/strobe system, not a speaker strobe system, and does not require a microphone installation.
- The VA will provide a copy of the original Edwards SDU program from the previous installation at the time of the upgrade, but cannot transfer this electronically due to policy restrictions.
The contracting entity is the 241-Network Contract Office 01, a federal office under the Department of Veterans Affairs. The primary point of contact for this solicitation is Yolanda Rankin, who can be reached at [email protected] or 978-890-2709. The notice remains active, with a response deadline extended to May 6, 2026, to accommodate questions and clarifications.
Contractors considering this opportunity should note the strict requirement for the Edwards EST4 panel, the defined scope of troubleshooting, and the warranty expectations. The project is designed to ensure system uniformity, regulatory compliance, and reliable fire safety for VA residents, with clear boundaries on contractor responsibilities and government support. Interested SDVOSBCs are encouraged to review the solicitation and attachments via the SAM.gov portal (Opportunity ID: caea56e47f264519be3bca492955d4b7) for full details and submission instructions.