Albeni Falls Dam (AFD) CO2 Cylinder Hydrostatic Testing - Amendment 1
Key Dates
Due Date
-
Posted Date
-
Agency & Value
Agency
W071 ENDIST SEATTLE
Contract Value
Not provided
Codes & Classification
Solicitation Number
W912DW26QA036
NAICS
811310 - Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
Classification Code
S202
Additional Details
Documents5
The U.S. Army Corps of Engineers, Seattle District, is soliciting qualified contractors for the inspection, hydrostatic testing, recertification, repair, replacement, transportation, and refilling of high-pressure carbon dioxide (CO2) cylinders used in the fire suppression systems at Albeni Falls Dam (AFD), located in Oldtown, Idaho. This procurement, identified by solicitation number W912DW26QA036 and classified under NAICS code 811310 (Commercial and Industrial Machinery and Equipment Repair and Maintenance), is set aside for Small Business Administration (SBA) eligible firms.
The primary objective of this contract is to ensure the continued safe and reliable operation of the fire suppression system protecting the electrical power generation equipment at Albeni Falls Dam. The system comprises forty-eight (48) active 75-pound CO2 cylinders, with a minimum reserve inventory of forty-eight (48) cylinders and up to fourteen (14) additional cylinders potentially available for inspection. The estimated total quantity of cylinders requiring service ranges from forty-eight (48) to sixty-two (62).
The scope of work requires the contractor to provide all necessary labor, supervision, materials, equipment, transportation, permits, and incidentals to perform the following services: pickup and transport of cylinders from the dam, discharge and reclamation of CO2, removal and inspection of valves, internal and external visual inspections for defects such as corrosion, pitting, dents, gouges, and thread damage, hydrostatic testing in accordance with Title 49 CFR 180.205 and other applicable Department of Transportation (DOT) regulations, evaluation of valve condition, refilling of serviceable cylinders, affixing recertification markings, and return delivery to the dam. All work must comply with federal regulations and industry standards.
The contract is structured as a Firm-Fixed-Price (FFP) agreement, with separately priced Contract Line-Item Numbers (CLINs) for repair and replacement actions, subject to government approval. The base CLIN covers transport, evaluation, hydrostatic testing, reporting, recertification, and refilling. Optional CLINs address rebuilding or replacing Kidde Type I valves, replacing complete cylinder assemblies, and replacing cylinders only, with quantities determined by the As-Found Inspection Report.
Contractors are required to submit an As-Found Inspection Report for each cylinder, detailing identification, inspection findings, hydrostatic test results, serviceability determination, valve condition, recommended repair or replacement actions, and estimated costs. No repairs or replacements may be performed without written government authorization, and detailed proposals must be submitted for approval prior to proceeding with optional CLINs.
Upon completion, recertification documentation must be provided for each cylinder and valve assembly, including serial numbers, test dates and results, work performed, serviceability determination, recertification date, and technician or facility identification. Quality assurance is a critical component; the government will inspect cylinders before release and upon return, verifying recertification markings, documentation completeness, physical condition, proper valve installation, and required safety labels. The government reserves the right to reject any cylinders that are improperly tested, documented, or certified.
The period of performance extends from contract award through 31 August 2026. Pickup and delivery operations are restricted to Monday through Thursday, 7:00 a.m. to 3:30 p.m. local time, excluding Fridays, weekends, and federal holidays. AFD personnel will stage cylinders at or near the public entrance to the powerhouse for contractor pickup.
The contracting entity is W071 ENDIST SEATTLE, a federal office under the Department of Defense, Department of the Army. Primary and secondary points of contact for this solicitation are Della S. Overton ([email protected], 206-764-6170) and Alex R. Marcinkiewicz ([email protected], 206-764-6170). The solicitation remains active, with a response deadline of 29 June 2026.
Contractors with expertise in commercial and industrial machinery repair and maintenance, particularly those experienced with high-pressure gas cylinders and DOT compliance, are encouraged to review the attached updated scope of work and price schedule for further details. This opportunity offers a stable, well-defined scope and clear quality expectations, making it suitable for firms capable of meeting rigorous federal safety and documentation standards.